kVA Calculator

Convert kVA to amps and amps to kVA for single-phase and three-phase systems. Useful for transformer, generator and UPS sizing.

—

kVA formulas

Single phase: kVA = V × I ÷ 1000  ·  I = kVA × 1000 ÷ V
Three phase: kVA = 1.732 × V × I ÷ 1000  ·  I = kVA × 1000 ÷ (1.732 × V)

kVA (kilovolt-amperes) is apparent power, voltage times current with no power factor. Transformers, generators and UPS units are rated in kVA because the heat in their windings depends on current, whatever the load's power factor. For three phase, V is the line-to-line voltage.

Worked examples

1. 75 kVA three-phase transformer, 480 V to 208Y/120 V

Primary: 75,000 ÷ (1.732 × 480) = 90.2 A
Secondary: 75,000 ÷ (1.732 × 208) = 208.2 A

This is the most common building transformer. Under NEC Table 450.3(B), primary-only protection at 125% would be 112.8 A, rounded up to the next standard size, 125 A. The secondary conductors must still be protected per NEC 240.21(C), usually by a 225 A or 250 A main in the panel they feed.

2. 25 kVA single-phase pole transformer

I = 25,000 ÷ 240 = 104.2 A

A 25 kVA utility transformer often serves several homes. Because residential loads are diverse and intermittent, utilities routinely load these well beyond nameplate for short periods.

3. Amps to kVA for a service

A 200 A, 120/240 V single-phase service: kVA = 240 × 200 ÷ 1000 = 48 kVA. A 400 A, 120/208 V three-phase service: kVA = 1.732 × 208 × 400 ÷ 1000 = 144 kVA.

4. Generator sizing

A building's measured peak is 160 A per phase at 480 V. Load: 1.732 × 480 × 160 ÷ 1000 = 133 kVA. At a 0.8 power factor that is 106 kW, so a 150 kW / 188 kVA standby generator leaves room for motor starting and growth.

Three-phase transformer full-load amps

kVA208 V480 V600 V
1541.6 A18.0 A14.4 A
3083.3 A36.1 A28.9 A
45124.9 A54.1 A43.3 A
75208.2 A90.2 A72.2 A
112.5312.3 A135.3 A108.3 A
150416.4 A180.4 A144.3 A
225624.5 A270.6 A216.5 A
300832.7 A360.8 A288.7 A

Full-load current at nameplate kVA, computed from the formula above.

kVA vs kW

kW = kVA × power factor. A 100 kVA load at a 0.85 power factor delivers 85 kW of real power, but the conductors and transformer carry the full current for 100 kVA. Size equipment in kVA and estimate energy use in kW. Converting between them needs the power factor; see the 3 phase power calculator to work with both.

Sizing tips

Frequently asked questions

How do I convert kVA to amps?

Single phase: A = kVA × 1000 ÷ V. Three phase: A = kVA × 1000 ÷ (1.732 × V), using line-to-line voltage.

How many amps is a 75 kVA transformer?

On the 208 V secondary of a three-phase 75 kVA transformer, full-load current is 75,000 ÷ (1.732 × 208) ≈ 208 A. On a 480 V primary it is about 90 A.

What is the difference between kVA and kW?

kVA is apparent power, volts times amps. kW is real power, kVA times power factor. Transformers and generators are rated in kVA because their heating depends on current, whatever the power factor.

What size transformer do I need?

Add up the load in kVA, allow for growth (often 20–25%), and pick the next standard size: 15, 30, 45, 75, 112.5, 150, 225 or 300 kVA for three-phase dry types. Overcurrent protection follows NEC 450.3(B).

How do I convert amps to kVA?

Single phase: kVA = V × A ÷ 1000. Three phase: kVA = 1.732 × V × A ÷ 1000. A 200 A, 120/240 V service is 240 × 200 ÷ 1000 = 48 kVA.