The three-phase voltage drop formula
VD = 1.732 × I × R × L ÷ 1000
VD% = VD ÷ VL-L × 100
I is the line current in amps. R is the conductor resistance in ohms per 1000 ft at 75 °C from NEC Chapter 9 Table 8. L is the one-way length in feet. The answer is the drop in line-to-line voltage, so compare it with the line-to-line system voltage.
Worked examples
1. 480 V feeder, 1/0 copper
100 A over 250 ft with 1/0 copper (0.122 Ω/kft):
VD = 1.732 × 100 × 0.122 × 250 ÷ 1000 = 5.28 V
VD% = 5.28 ÷ 480 = 1.10%
Well within 3%. At 480 V, three-phase feeders can run a long way before voltage drop matters.
2. 208 V rooftop unit
A 40 A RTU, 150 ft from the panel, on 8 AWG copper (0.764 Ω/kft):
VD = 1.732 × 40 × 0.764 × 150 ÷ 1000 = 7.94 V → 3.82%
That is over 3%. Upsizing to 6 AWG (0.491 Ω/kft) gives 5.10 V, or 2.45%. If you upsize ungrounded conductors for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion.
3. 600 V feeder in aluminum (Canada)
150 A over 300 ft on 3/0 aluminum (0.126 Ω/kft):
VD = 1.732 × 150 × 0.126 × 300 ÷ 1000 = 9.82 V → 1.64%
Under CEC Rule 8-102 this is within the 3% feeder limit. For metric lengths, use the Canadian voltage drop calculator.
Why voltage matters so much
For the same load in kVA, current falls as voltage rises, and the allowed drop in volts rises too. Moving a load from 208 V to 480 V cuts the current by 57% and more than doubles the allowable drop, so percent drop falls by about 81%. This is the main reason large buildings distribute at 480 V or 600 V.
Sizing a three-phase feeder for voltage drop
Rearranging the formula gives the largest resistance you can accept:
Rmax = (V × VD%max) × 1000 ÷ (1.732 × I × L)
For the RTU above at 3%: (208 × 0.03 × 1000) ÷ (1.732 × 40 × 150) = 0.600 Ω/kft. The smallest copper size at or below that is 6 AWG (0.491). The wire size calculator does this automatically and also checks ampacity.
Motors and voltage drop
Motors draw five to seven times full-load current when starting, so running drop of 3% can become a 15–20% dip at start. That can stop contactors pulling in. For large motors on long runs, check starting drop too, or use a soft starter or VFD.
Related formulas
See the voltage drop formula guide for the K-factor (circular mil) method, and the single-phase voltage drop calculator for 120/240 V circuits.