Ampacity Chart & Derating Calculator

Apply NEC ambient temperature correction and conductor-count adjustment to Table 310.16 ampacity. Pick a wire, its insulation column, the ambient temperature and the number of current-carrying conductors.

—
Table ampacity—
Temp. factor—
Adjustment factor—

The derating formula

Adjusted ampacity = Table 310.16 ampacity × temperature correction factor × adjustment factor

The result is then capped by the termination temperature rating (usually the 75 °C column) and, for 14–10 AWG, by the 240.4(D) overcurrent limits. Full table values are in the wire ampacity chart.

Ambient temperature correction (NEC Table 310.15(B)(1))

Ambient (°C)60 °C75 °C90 °C
≤ 101.291.21.15
11–151.221.151.12
16–201.151.111.08
21–251.081.051.04
26–30111
31–350.910.940.96
36–400.820.880.91
41–450.710.820.87
46–500.580.750.82
51–550.410.670.76
56–60—0.580.71
61–65—0.470.65
66–70—0.330.58
71–75——0.5
76–80——0.41
81–85——0.29

More than three current-carrying conductors (NEC Table 310.15(C)(1))

ConductorsAdjustment
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Worked examples

1. Six 10 AWG THHN in a warm mechanical room

10 AWG copper THHN is 40 A in the 90 °C column. Ambient is 40 °C (factor 0.91) and there are six current-carrying conductors (80%):

40 × 0.91 × 0.80 = 29.1 A

That is below the 75 °C limit of 35 A, so 29.1 A is the ampacity. 240.4(D) would cap protection at 30 A anyway. NEC 240.4(B) allows rounding up to a 30 A breaker for a non-standard ampacity, but not on a multioutlet branch circuit supplying cord-and-plug receptacles, where you would use 25 A or upsize to 8 AWG.

2. 12 AWG through a hot attic

Three current-carrying 12 AWG THHN conductors pass through an attic at 50 °C. 30 A × 0.82 = 24.6 A, which still supports a 20 A breaker. With six conductors bundled in the same space: 30 × 0.82 × 0.80 = 19.7 A, which is under 20 A, so you would need 10 AWG or a separate run.

3. A feeder in 75 °C wire

Four 4/0 aluminum XHHW conductors (a 3-phase feeder with a neutral carrying non-linear load, so it counts): 4/0 Al 90 °C is 205 A, × 0.80 = 164 A. That fits a 150 A breaker, or 175 A under 240.4(B) where the ampacity is not a standard size and the next standard rating is used. Check whether your design meets 240.4(B)'s conditions before rounding up.

Tips to avoid derating

After derating, confirm the raceway with the conduit fill calculator and the run with the voltage drop calculator.

Frequently asked questions

What is ampacity derating?

Reducing a conductor's table ampacity for conditions hotter than the table assumes: ambient above 30 °C (NEC 310.15(B)) or more than three current-carrying conductors together (310.15(C)(1)). Both factors multiply.

Can I derate from the 90 °C column?

Yes. With 90 °C insulation such as THHN or XHHW-2 you may apply the factors to the 90 °C ampacity. The result can't exceed the ampacity of the lowest-rated termination, usually the 75 °C column (NEC 110.14(C)).

Does the neutral count as a current-carrying conductor?

Not on a single-phase 3-wire circuit or a balanced 3-phase 4-wire circuit with linear loads, per NEC 310.15(E). It does count on a 3-wire circuit from a 4-wire wye system, and when the major part of the load is non-linear (LED drivers, electronics). Equipment grounding conductors never count.

Does derating apply to short conduit sleeves?

No. Under NEC 310.15(C)(1)(b), adjustment factors do not apply to conductors in raceways 24 in or shorter.

What is the rooftop adder?

NEC 310.15(B)(2) adds 33 °C to the ambient for raceways or cables exposed to sunlight less than 7/8 in above a roof. XHHW-2 is exempt. Raise conduits off the roof to avoid it.