Wire Size Calculator

Size a conductor for ampacity and voltage drop in one step. Enter the load, the run length and your terminal rating, and the calculator returns the smallest copper or aluminum wire that satisfies both.

—
Required ampacity—
Size by ampacity—
Size by voltage drop—
Drop at recommended—

NEC Table 310.16 (≤3 current-carrying conductors, 30 °C ambient), 240.4(D) limits, Chapter 9 Table 8 resistance. No derating applied.

How the wire size calculator decides

Picking a wire size is two separate checks, and the larger answer wins:

  1. Ampacity. The conductor must carry the load without overheating. The calculator multiplies continuous loads by 125%, then finds the smallest size in NEC Table 310.16 whose ampacity in your chosen temperature column meets that value. It also applies the small-conductor limits of 240.4(D): 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper (15 A and 25 A for 12 and 10 AWG aluminum).
  2. Voltage drop. The conductor must deliver enough voltage at the far end. Using the actual load current (not the 125% value) and NEC Chapter 9 Table 8 resistance, it finds the smallest size that keeps the drop at or under your limit, 3% by default.

On short runs ampacity controls; on long runs voltage drop usually controls. The result tells you which one did.

Formulas

Required ampacity = load × 1.25 (continuous) or load × 1.00
VD% = k × I × R × L ÷ 1000 ÷ V × 100, k = 2 (1-ph) or 1.732 (3-ph)

Worked examples

Example 1: 40 A load, 75 ft, 240 V

A 40 A non-continuous load on copper with 75 °C terminals. Table 310.16 shows 8 AWG copper at 50 A in the 75 °C column, so 8 AWG passes ampacity. Voltage drop on 8 AWG: 2 × 40 × 0.764 × 75 ÷ 1000 = 4.58 V, or 1.91% of 240 V. Both checks pass: 8 AWG copper.

Example 2: 48 A EV charger, 150 ft, 240 V

EV chargers are continuous loads (NEC 625.41), so the conductor needs 48 × 1.25 = 60 A. 6 AWG copper is 65 A at 75 °C. Voltage drop: 2 × 48 × 0.491 × 150 ÷ 1000 = 7.07 V, or 2.95%, just under 3%. Answer: 6 AWG copper on a 60 A breaker. A few more feet and voltage drop would push it to 4 AWG.

Example 3: 16 A at 120 V, 150 ft

Ampacity alone allows 12 AWG. But 12 AWG drops 2 × 16 × 1.93 × 150 ÷ 1000 = 9.26 V (7.7%). 8 AWG still drops 3.06%, so the calculator lands on 6 AWG for a 3% limit. This is a strong case for running the circuit at 240 V or adding a subpanel.

Choosing the temperature column

NEC 110.14(C) says the conductor ampacity you use cannot exceed the rating of the lowest-rated termination. For circuits of 100 A or less, or conductors 14 AWG through 1 AWG, use the 60 °C column unless the equipment is listed and marked for 75 °C, which most modern breakers and devices are. Above 100 A, use 75 °C. THHN's 90 °C rating is used as the starting point for derating, not as the final ampacity.

Quick reference: common circuit sizes (copper, 75 °C)

BreakerMinimum copperMinimum aluminum
15 A14 AWG12 AWG
20 A12 AWG10 AWG
30 A10 AWG8 AWG
40 A8 AWG8 AWG*
50 A8 AWG* / 6 AWG6 AWG*
60 A6 AWG4 AWG
100 A3 AWG1 AWG
200 A3/0250 kcmil

*Only with all terminations rated 75 °C. Before voltage drop and derating. Dwelling services and feeders may use NEC 310.12 (83% rule) instead, which allows 2/0 copper or 4/0 aluminum for a 200 A service.

What this calculator does not cover

It does not apply ambient temperature correction, bundling adjustment, rooftop adders, motor rules (Article 430), or the 310.12 dwelling service table. It also does not size the equipment grounding conductor (Table 250.122). Use it to get the starting point, then apply the rules for your installation. For a conduit to carry the result, use the conduit fill calculator.

Frequently asked questions

What size wire do I need for 30 amps?

10 AWG copper is the usual minimum for a 30 A circuit: NEC 240.4(D) limits 10 AWG copper to 30 A overcurrent protection. On long runs, voltage drop may push you to 8 AWG. For aluminum, 8 AWG (35 A in the 60 °C column) is the usual minimum, since 240.4(D) limits 10 AWG aluminum to 25 A.

What size wire for a 50 amp circuit?

6 AWG copper (65 A at 75 °C) is the common choice; 8 AWG copper is only 50 A at 75 °C and 40 A at 60 °C, so it works only when every termination is rated 75 °C. For aluminum, use 4 AWG (65 A at 75 °C).

Why does the calculator use the 75 °C column by default?

NEC 110.14(C) limits ampacity to the lowest temperature rating of any termination. Most breakers and lugs are rated 75 °C. Equipment rated 100 A or less, or for 14–1 AWG, defaults to 60 °C unless marked otherwise. The 90 °C column is mainly used as the starting point for derating.

What is a continuous load?

A load expected to run at maximum current for three hours or more, such as EV chargers, lighting in stores and electric heat. Conductors for continuous loads must have an ampacity of at least 125% of the load (NEC 210.19(A)(1), 215.2(A)(1)).

Does this include derating for bundled wires or hot attics?

No. The result assumes no more than three current-carrying conductors and a 30 °C ambient. Use the ampacity derating calculator when you have more conductors in a raceway or high ambient temperatures.

Can I use 14 AWG on a 20 amp breaker?

No. NEC 240.4(D) limits 14 AWG copper to 15 A protection, even though its 75 °C table ampacity is 20 A. 12 AWG copper is limited to 20 A and 10 AWG copper to 30 A.